Series: PGM-8325
Neutral Grounding Resistor Monitor
The PGM-8325 Neutral Grounding Monitor is used on
resistance-grounded systems up to 25 kVac to monitor the integrity of the neutral-to-ground path. It measures current and voltage in a transformer or generator neutral-to-ground connection and continuity of the neutral-grounding resistor (NGR). The PGM-8325 coordinates these three measurements to detect a loose connection, corrosion, ground-fault, or NGR failure, and provides one alarm or trip output contact.
Electrical Characteristics
Access specifications, certifications, check availability and order parts below: Check distributor stock availability by clicking on the [CHECK] link. View certification PDF files by clicking on the certification logo. View the part details by clicking on the part number. To order sample parts, click on the [ADD] link. Click on the 'Key' button to view definitions for each column header. Sort parts by clicking on the column you wish to sort by. |
|