Series: PGM-8325
Neutral Grounding Resistor Monitor
The PGM-8325 Neutral Grounding Monitor is used on resistance-grounded systems up to 25 kVac to monitor the integrity of the neutral-to-ground path. It measures current and voltage in a transformer or generator neutral-to-ground connection and continuity of the neutral-grounding resistor (NGR). The PGM-8325 coordinates these three measurements to detect a loose connection, corrosion, ground-fault, or NGR failure, and provides one alarm or trip output contact.


Electrical Characteristics

Access specifications, certifications, check availability and order parts below:

Check distributor stock availability by clicking on the [CHECK] link. View certification PDF files by clicking on the certification logo. View the part details by clicking on the part number. To order sample parts, click on the [ADD] link. Click on the 'Key' button to view definitions for each column header. Sort parts by clicking on the column you wish to sort by.


CatalogNo Certs. Supply
Voltage
(VAC)
Relay
Contacts
Approvals Stock Sample
Cart
PGM-8325 120 One Form A (N.O.) CSA n/a n/a
PGM-8325-E 240 One Form A (N.O.) CSA n/a n/a