RM2000 - RM 2000 Series

Series: RM 2000
Questions? Contact Littelfuse Support
External overview image
Roll Over to Zoom
Disclaimer Notice

Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The RM2000 is a motor-monitoring device to be used in conjunction with the 777 family of products (excluding the P1 Series), 77C family of products and the Model 601 voltage monitors, via Modbus protocol with a communications module. The RM-2000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly, motor monitoring.
The RM2000 has membrane keypad controls which allow both monitoring and control of a 777 relay through an RS-485 network using Modbus RTU protocol. A second communication port allows monitoring and control of up to 99 RM-2000 devices from a PLC, DCS, or SCADA system or a PC with Solutions software installed. The RM2000 will act as a repeater for its motor protector when accessed from the host computer or PLC. In addition to the monitoring functions, the RM2000 can be used to reset a tripped relay.
The RM2000 is easily mounted remotely and improves safety for service and operations personnel by allowing them to control and monitor the device without opening the electrical cabinet. Using the RM2000 is a simple, cost-effective method for aiding compliance with arc flash safety regulations. The enclosure and keypad assembly is water and ultraviolet light resistant.
Property (Mouseover for details) Value
Input Voltage (V) 115 Vac
Input Tolerance (%) ±10%
Maximum Input Power 3
Input AC Line Frequency (Hz) 50 / 60
Protection Class NEMA 3R/UL Type 12
Memory Capacity Stores last 4 faults with time and date stamp; includes voltage and current at time of trip
Communications Protocol Modbus RTU
Communications Interface RS-485
Communications Range 50 ft; 4000 ft with separate isolated power supply
Communications Baud Rate (Bps) 300 - 28800
Address A001 - A099
Termination Type 3 in.-lbs.
Mounting Method Surface mountable on backplane using 4 screws
Operating Temperature -20° to 70°C (-4° to 158°F)
Storage Temperature (F/C) -30° to 70°C (-22° to 158°F)
Humidity Up to 85% non-condensing
Dimensions 6.4 H x 6.1 W x 1.1 D in. (162.6 x 154.9 x 27.9 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.