FPS Series - Feeder Protection System

The FPS (Feeder Protection System) is a feeder-protection relay that provides current, voltage, and temperature protection for feeder applications. It offers integrated breaker or contactor control, data logging, and a complete metering package. The FPS is typically used in processing, manufacturing, petroleum, chemical, mining, forestry, water, and waste treatment applications.

FEATURES

IEEE #

BENEFITS

Overload

49, 51

Long-time overcurrent provides thermal protection for feeder or load

Inverse-time overcurrent

50, 51

Coordination using IEEE and IEC Curves

Definite-time overcurrent

50, 51

Instantaneous overcurrent to detect catastrophic failure

Current unbalance/
Phase loss/Phase reverse

46

Detects an open or high-impedance phase

Reduced overcurrent mode


Minimizes arc-flash hazards during maintenance to meet NEC 240,87 (B) (3)

Ground fault

50G/N, 51G/N

Inverse and definite time. Early insulation-failure detection.

RTD temperature

38, 49

Optional protection (MPS-RTD module) for load-temperature monitoring

Overvoltage

59

Limits stress to insulation

Undervoltage

27

Detects a damaging brown-out condition

Voltage unbalance

47

Detects unhealthy supply voltage

Two setting groups

Minimizes Arc-Flash hazards during maintenance

Breaker control

Allows local and remote operation; reduces component count

Metering

Displays the measured and calculated parameters

Data logging

On-board 64-event recorder helps with system diagnosis

Communications

Remotely view measured values, event records, & reset trips

Conformal coating

Internal circuits are conformally coated to protect against corrosion and moisture

Access specifications, certifications, check availability and order parts below

Catalog #Supply
Voltage
(VAC)
Supply
Voltage
(VDC)
Relay
Contacts
ApprovalsAnalog Output (mA)CommsCompare
FPS-CTU-01-0065 - 26580 - 275Three Form A (N.O.); Two Form C (N.O./N.C.)CSA4-20RS/TIA-485
FPS-CTU-02-0065 - 26580 - 275Three Form A (N.O.); Two Form C (N.O./N.C.)CSA4-20RS/TIA-485
DeviceNet
FPS-CTU-03-0065 - 26580 - 275Three Form A (N.O.); Two Form C (N.O./N.C.)CSA4-20RS/TIA-485
Profibus
FPS-CTU-04-0065 - 26580 - 275Three Form A (N.O.); Two Form C (N.O./N.C.)CSA4-20RS/TIA-485
Ethernet
FPS-OPI-01-00CSA

pdf icon FPS Datasheet

pdf icon FPS Manual

The Feeder Protection System (FPS) is a modular system with integrated protection, control, metering, and data-logging functions.

SE-Comm-RIS v4.1 Software

FPS MPS RTD CAD Drawing

pdf icon FPS DeviceNet Manual

This document describes the DeviceNet features supported by the FPS. The FPS supports Explicit and Polled I/O. It does not support the Unconnected Message Manager (UCMM).

pdf icon FPS ModbusTCP EthernetIP Manual

The Ethernet interface supports Modbus TCP and EtherNet/IP. Part A of this manual describes the features of the Modbus TCP version of Ethernet.

pdf icon FPS MPS Profibus Manual

pdf icon TN MA-13 PMA-13 Multilin 169 269 Adapter MPS

pdf icon TN MP14 Using One OPI for Multiple Motors

pdf icon TN MP13 MPS Voltage Sequence Two PT Connection

pdf icon TN MA24 GE Multilin 46 for MPS


  • Showing 7 items