TL120A5T - TL Series

Series: TL Questions? Contact Littelfuse Support
Littelfuse HVAC Relays
The TL Series provides protection against short cycling of a compressor. At the end of each operation, or whenever power is lost, a lockout delay is initiated. This lockout delay prevents restarting of the compressor until the head pressure has equalized. Compressor relay chatter due to thermostat bounce is eliminated by use of optional one second delay-on-make. The TL Series should not be used with cooling anticipator resistors or solid-state switches. (See the TA Series).


Operation (Lockout)
Lockout: On initial closure of S1, the compressor relay energizes immediately (or after an optional 1s delay). When the S1 opens or input voltage is interrupted, the output opens and remains open for the lockout time delay. During this lockout time delay period, the compressor relay cannot be re-energized.
Reset: The lockout time delay cannot be reset. After the time delay is completed, the unit automatically resets.

Property (Mouseover for details) Value
Input Voltage (V) 120VAC
Input Tolerance (%) ±20%
Input AC Line Frequency (Hz) 50/60Hz
Output Load Rating (VA) 0.5A at 60°C
Minimum Output Load Current (A) ≤40mA
Output Voltage Drop (V) ≅4.2V @ 0.5A
Time Delay Tolerance (%) -15% - 35%
Time Delay Option 1s delay-on-make eliminates contactor chatter due to thermostat bounce
Lockout and Random Start Delays 5m fixed
Initiate Time (ms) ≤8ms
Insulation Resistance ≥100 MΩ
Dielectric Breakdown ≥2000V RMS terminals to mounting surface
Inush 10A at 60oC
Circuitry Encapsulated
Termination Type 0.25 in. (6.35mm) male quick connect terminals
Mounting Method Surface mount with one #10 (M5 x 0.8) screw
Operating Temperature -40° to 70°C (-40°F to 158°F)
Storage Temperature (F/C) -40° to 85°C (-40°F to 185°F)
Humidity 95% relative non-condensing
Dimensions 2.00 x 2.00 x 1.21 in. (50.8 x 50.8 x 30.7mm)
Weight (lbs/g) ≅2.4oz (68g)
Sample capable No