TS6123P - TS2 / TS6 Series

Littlefuse Interval Relays
The TS2 Series is designed for 24, 120 or 230VAC and the TS6 Series is designed for 12 or 24VDC. These series are capable of controlling load currents of up to 1A steady state, 10A inrush. Encapsulated circuitry and the reliability of a ±2% repeat accuracy make the TS2 and TS6 ideal for cost sensitive applications.


Operation (Interval)
Upon application of input voltage, the time delay begins. The output energizes during the time delay. At the end of the time delay, the output de-energizes and remains de-energized until input voltage is removed.
Reset: Removing input voltage resets the time delay and the output.

Property (Mouseover for details) Value
Input Voltage (V) 12VDC
Input Tolerance (%) ±15%
Input DC Ripple (%) ≤10%
Output Type Solid state
Output Form NO closed during timing
Output Load Rating (VA) 1A steady state; 10A inrush at 60°C
Output Voltage Drop (V) ≅1V @ 1A
Time Delay Type Analog circuitry
Time Delay Range 2 - 60s externally adjustable
Time Delay Tolerance (%) ≤±10%
Reset Time (ms) ≤150ms
Repeat Accuracy (%) ±2% or 20ms whichever is greater
Setpoint vs Ambient Temperature and Operating Voltage (%) ≤ ±10%
Insulation Resistance ≥100 MΩ
Dielectric Breakdown ≥2000V RMS terminals to mounting surface
DC Operation Positive switching mode
Circuitry Encapsulated
Power Consumption ≤1W
Termination Type 0.25 in. (6.35mm) male quick connect terminals
Mounting Method Surface mount with one #10 (M5 x 0.8) screw
Operating Temperature -40° to 75°C (-40°F to 167°F)
Storage Temperature (F/C) -40° to 85°C (-40°F to 185°F)
Humidity 95% relative non-condensing
Dimensions 2.00 x 2.00 x 1.21 in. (50.8 x 50.8 x 30.7mm)
Weight (lbs/g) ≅2.4oz (68g)
Sample capable No