PGR-3100 - Ground-Fault Indication System

The PGR-3100 indicates the presence of voltage on each phase of a three-phase system. The LEDs on the panel illuminate when voltage is present. When a ground-fault occurs, the voltage on the faulted phase reduces to ground potential, causing the LEDs for the faulted phase to dim and the LEDs for the unfaulted phases to become brighter. Ungrounded ac systems are required by the National Electrical Code (NEC®) Article 250.21(B) and the Canadian Electrical Code Part 1, Section 10-106 (2) to have ground detectors, such as the PGR-3100, installed on the system. External potential transformers (PTs) can be used to step down system voltage, allowing the PGR-3100 to be applied to any system voltage. PTs are not required for system voltages up to 600 Vac. Also available mounted in NEMA 4 enclosure.

FEATURES

BENEFITS

NEC® and CEC Code compliant

Meets National Electrical Code (NEC®) Article 250.21(B) and Canadian Electrical Code Part 1, Section 10-106 (2) requirements for ungrounded systems

Phase LEDs

Indicates presence of a ground fault and the faulted phase as well as phase-to-ground voltage on an energized bus

Redundant LEDs

Redundant long-life LEDs (two per phase) to ensure reliability

Lamp test button

Verifies LEDs are operating

Access specifications, certifications, check availability and order parts below

Catalog #CertificatesSupply
Voltage
(VAC)
Supply
Voltage
(VDC)
Relay
Contacts
ApprovalsStockSamples
PGR-3100ul600 VacN/AN/ACSA; UL