Resistance Grounded Systems
Resistance grounding is the only method of grounding that solves the problems commonly associated with both ungrounded systems and solidly grounded systems. The name is derived from the addition of a resistor between the system neutral and ground. The specifications of the resistor are user determined to achieve a desired ground fault current, which must be greater than the system capacitive charging current (explained later in this section).

FIGURE 7
|
|---|
A protection relay for resistance grounded systems is used to detect a ground fault and to monitor the neutral-to-ground connection. It can be used to provide alarms or to trip the faulted feeder from service during a ground fault. The relay can provide a pulsing circuit that can be used to locate the ground fault. The relay can also alarm or trip if the neutral-to-ground path fails. For systems 5 kV and less, high-resistance grounding can be used. High-resistance grounding typically limits the resistor current to 10 A or less. By doing so, the ground fault can remain on the system, given that the system is rated for the voltage shift.
For systems 2.4 kV and higher, low-resistance grounding systems can be used. Typically in those systems the ground fault current is 25 A or above and is cleared within 10 s.






