Solidly Grounded Systems
Due to the problem of ungrounded systems, a shift in philosophy occurred and designs moved from ungrounded to grounded systems. In most cases, the type of grounding system chosen was solidly grounded. A solidly grounded system is a system of conductors in which at least one conductor or point is intentionally grounded (usually the neutral point of transformer or generator windings). The problem with the direct connection is that ground fault current can be excessive, causing Arc-Flash hazards, extensive equipment damage, and possible injury to personnel.

FIGURE 5
|
|---|
Figure 6 illustrates an example of the dangers associated with solidly grounded systems. In this example, a ground-fault occurs and the overcurrent protection is set at 600 A.

FIGURE 6
|
|---|
Aside from converting this solidly grounded system to resistance grounding, the best way to prevent damage is to detect low-level ground leakage prior to it becoming a ground fault. In order to accomplish this, the protection relay must be able to sense a low-level ground leakage without nuisance tripping.
In modern facilities, equipment often generates noise or harmonics that may interfere with a protection relay’s ability to function properly. For example, the noise or harmonics may be higher than the desired ground-fault relay settings, causing the relay to falsely operate when there is no fault on the system. The protection relay must be able to filter out noise or harmonics to provide reliable protection.






