Roll Over to Zoom
 

The FPS (Feeder Protection System) is a feeder-protection relay that provides current, voltage, and temperature protection for feeder applications. It offers integrated breaker or contactor control, data logging, and a complete metering package. The FPS is typically used in processing, manufacturing, petroleum, chemical, mining, forestry, water, and waste treatment applications.

Features & Benefits:

  • Eighteen protective functions to extend the life of transformers and feeder cables
  • Meters current, voltage, power, temperature, and more
  • Inverse-time (including IEC and IEEE curves) and definite-time overcurrent and earth-fault protection
  • Breaker or contactor control - integrated OPEN and CLOSE command keys
  • Large 80-character vacuum-fluorescent display
  • Eight digital inputs, five relay outputs, one analog input and output
  • RTD module can be installed remotely (up to 1,200 m) to simplify wiring
  • CSA Class 1 Zone 2 hazardous-location certified OPI and RTD modules
  • Standard Modbus RTU and Allen-Bradley DF1 RS-485 communications
  • Optional Modbus TCP and Ethernet/IP, DeviceNet, PROFIBUS communications
  • Free SE-Comm-RIS PC-interface software
  • Conformally coated circuit boards
  • 10-year warranty
Property (Mouseover for details) Value
Analog Output Current mA 4 - 20
Communications RS/TIA-485
Relay Contacts Config 3 Form A (N.O.); 2 Form C (N.O./N.C.)
Supply Voltage ac 65 - 265
Supply Voltage dc 80 - 275
IEEE Device Numbers 1 - 2 - 3 - 5 - 19 - 27 - 37 - 38 - 46 - 47 - 49 - 50 - 50G - 50N - 51 - 51G - 51N - 55 - 59 - 74 - 81 - 86 - 94
Relay Contacts Operation Fail-safe / Non Fail-safe
Weight (lbs/g) 0 Kg
Analog Inputs One 4-20 mA
Conformally coated Standard
Frequency 50; 60; ASD
GF Trip Level Range pct 5 - 100% of CT-Primary Rating
GF Trip Time s 0.0 - 100.0
Harmonic Filtering Standard (DFT)
Reset Type Front-panel switch/Remote N.O. Contact
Temp Sensor Config Up to 8 with MPS-RTD
Digital Inputs 8