The FPU-32 is a feeder-protection relay that provides integrated protection, metering, and data-logging functions.

Features/Benefits:
• Eight functions to protect against overcurrent, earthfaults, and phase loss; standard LSIG protection plus unbalance and thermal protection
• IEC and IEEE overcurrent protection curves to coordinate with upstream and downstream devices
• Thermal element active below overcurrent pickup
• Definite- and inverse-time ground-fault protection

Two set-point groups can be used for:
• Maintenance setting to reduce fl ash hazard
• Two different loads
• Compact size for ease of installation and for retrofit applications
• Conformally coated circuit boards
Property (Mouseover for details) Value
Analog Output Current mA 4 - 20
Communications RS/TIA-232 - DeviceNet
Relay Contacts Config 3 Form C (N.O./N.C.)
Supply Voltage ac 65 - 265
Supply Voltage dc 80 - 275
IEEE Device Numbers 26 - 46 - 49 - 50 - 50G - 50N - 51 - 51G - 51N - 74 - 86
Relay Contacts Operation Fail-safe / Non Fail-safe
Weight (lbs/g) 0 Kg
Conformally coated Standard
Frequency 50; 60; ASD
GF Trip Level Range pct 5 - 100% of CT-Primary Rating
GF Trip Time s 0.0 - 100.0
Harmonic Filtering Standard (DFT)
Reset Type Front-panel switch/Remote N.O. Contact
Temp Sensor Config Single
Digital Inputs 1
To request product environmental information, please complete the Product Environmental Information Request Form.