MP8000 - MP8000 Series

Series: MP8000
Questions? Contact Littelfuse Support
External overview image
Roll Over to Zoom
 

The MP8000 is an advanced motor protection electronic overload relay that is fully programmable via Bluetooth* using an iPhone* or Android* smartphone or tablet with the Littelfuse App. It is easy to use and arc-flash safety is increased because the app allows settings to be modified and real-time operational information viewed. Viewing operational information and faults on the app does not require the user to open the control panel. The MP8000 protects any motor drawing 0.5-1,000 full load Amps (external CTs are required above 100 Amperes). It is designed for single or 3-phase systems with operating voltages of 90-690 VAC (use of external potential transformers can extend upper voltage range above 690 VAC). Common applications include conveyor systems, HVAC equipment, saws and grinders, fan motors, and almost any pumping application.

Protection is unsurpassed by combining overload, voltage, phase loss and reversal, voltage and current imbalance, power monitoring, and underload in one package. For standalone applications, the Bluetooth* interface can be used when paired with a smartphone or tablet. The units also feature an Ethernet communications port that can be used to form an Ethernet Modbus TCP/IP or Ethernet/IP network. Units can be remotely monitored and controlled from a PC, or SCADA system, and data logging through a PC with the optional MP8000 software or other software program using the MP8000 memory map. This capability allows for a simple cost-effective way to further enhance arc-flash safety.

*Bluetooth, iPhone and Android are registered trademarks of their respective owners.

Property (Mouseover for details) Value
Supply Voltage ac 85 - 264
Input Voltage (V) 90 - 690 Vac (use of external PTs can extend the upper range above 690 Vac)
Input AC Line Frequency (Hz) 50 / 60
Output Form Control relay: SPST - Form A; Auxilliary relay: SPDT - Form C
Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 5 A @ 240 Vac
Full Load Amp Range (A) 0.5 - 10 direct; 100+ (external CTs required)
Timing Accuracy (%) 2% ±0.5 s
Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (2 to 100 A direct)
Voltage Accuracy (%) ±1% of setting ±2 Vrms
Overcurrent Trip Class 02 - 60 or linear
Current Accuracy (%) ±2% (2 to 100 A direct)
Ground Fault Accuracy (%) ±2%
Sensor Hole Size Max conductor size: 0.63 in (with insulation)
HP/kW Accuracy (%) ±5% of setting ±5 W
Power Consumption <5 W
Short Circuit (kA) 100 symmetrical at 690 V ac
Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
Protection Class IP20 (finger safe)
Pollution Degree 3
Memory Capacity Stores last 1000 faults with time and date stamp; includes conditions at time of trip
Communications Protocol Ethernet Modbus TCP/IP or Ethernet/IP
Communications Interface Bluetooth; Ethernet Modbus TCP/IP or Ethernet/IP
Communications Range Bluetooth range is up to 30 ft (range may be reduced depending on the smartphone/tablet used; enclosure type; or environmental factors)
Termination Type Torque: Depluggable terminal blocks: 7 in-lbs; Earth ground: 7.9 in-lbs
Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature -40° to 70°C (-40° to 158°F)
Storage Temperature (F/C) -40° to 85°C (-40° to 185°F)
Humidity 10 - 95% non-condensing per IEC 68-2-3
Dimensions 2.91 H x 4.08 W x 4.79 D in. (73.9 x 103.6 x 121.7 mm)
Weight (lbs/g) 0 Kg
Conformally coated Yes
Frequency 50/60 Hz
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.