High-resistance grounding prevents many of the problems that are associated with ungrounded and solidly grounded electrical distribution and utilization systems. High-resistance grounding can limit point-of-fault damage, eliminate transient overvoltages, reduce the arc-flash hazards, limit voltage exposure to personnel, and provide adequate tripping levels for selective current-based ground-fault detection and coordination. The Littelfuse Neutral Grounding Resistor System is a neutral grounding resistor (NGR), current transformer, and sensing resistor installed in a NEMA 3R enclosure used to high-resistance ground transformers and generators. The NGR system is designed for use with Littelfuse Neutral Grounding Resistor Monitors for complete system grounding and grounding protection. The NGR series – US systems are designed for use in US applications and all other parts of the world, not including Canada. For applications in Canada, please use the NGR series – Canada.

Property (Mouseover for details) Value
CT secondary current Amps 0.05
Input Voltage (V) 4160
Input Current Range (A) 15
Input Impedance (Ohms) 160.3
Response Time (ms) Continuous
Sense Resistance (Ohms) ER-5WP
Mounting Method Floor Mount
built in CTs No
Frequency 60
NEMA Rating 3R; Weather Protected Sensing Resistor
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.