601575 - 601 Series – Three-Phase Voltage & Frequency Monitor Series

External overview image
Roll Over to Zoom
Disclaimer Notice

Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The Model 601 is a fully-programmable voltage monitor designed to protect 3-phase motors. It can be used as a stand-alone product or networked with an RM-1000, RM-2000, PLC, computer or SCADA system.


When a harmful condition is detected, the 601’s output relay is deactivated after the specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for the programmed restart delay (RD2).


Eleven (11) setpoints are viewable with the 3-digit LED display or from a networked device:

    low voltage
      high voltage
        voltage unbalance
          low frequency
            high frequency
              RS485 address
                trip delay for voltage/frequency faults
                  trip delay for single-phase faults
                    rapid-cycle timer (RD1)
                      restart delay after all faults (RD2)
                        type of restart after all faults (manual or automatic)

                        Six (6) parameters are viewable while the motor is running:

                          L1-L2 voltage
                            L2-L3 voltage
                              L1-L3 voltage
                                average voltage
                                  voltage unbalance (%)
                                    voltage frequency (%)


                                    When used with the RS485MS-2W communications module, the 601 can communicate with most Modbus RTU master devices. Voltage conditions can be monitored and setpoints can be changed remotely using Solutions software, an RM-1000, RM-2000 or other device.

Property (Mouseover for details) Value
Input Voltage (V) 500 - 600 Vac
Maximum Input Power 5
Input AC Line Frequency (Hz) 50 / 60
Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac
Timing Accuracy (%) 5% ±1 s
Rapid Cycle Timer (s) 0; 2 - 500 s
Restart Delay Range Restart Delay After All Faults: 2 - 500 s
Repeat Accuracy (%) Voltage: ±0.5%
Trip Delay Range Voltage/Unbalance/Frequency faults/single-Phase faults: 1 - 50 s
Overvoltage Reset Voltage (%) 97% of HV Setting
Undervoltage Reset Voltage (%) 103% of LV Setting
Voltage Unbalance Reset (%) UB Setting -1%
Voltage Accuracy (%) ±1%
Over/Under Frequency (%) Low: 35 Hz - HF setting; High: LF setting - 75 Hz
Protection Class IP20; NEMA 1 (finger safe)
Address A01 - A99
Termination Type Torque: 7 in-lbs
Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature -20° to 70°C (-4° to 158°F)
Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
Humidity 95% non-condensing per IEC 68-2-3
Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes