The 102A series is a three-phase, auto-ranging, dual-range voltage monitor that protects 190–600 V ac, 50*/60 Hz motors regardless of size. This monitor provides a user-selectable nominal voltage setpoint and will automatically select between the 200 V and 400 V range. A unique microcontroller-based voltage and phase-sensing circuit constantly monitors the three-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels. The 102A monitor includes advanced, single LED diagnostics with five different light patterns that distinguish between faults and normal conditions. LED indications include normal operation, power-up restart delay, reverse-phase trip, unbalance/single-phase trip, and high- or low-voltage trip.
*Note: 50 Hz will increase all delay times by 20 %
Proprietary microcontroller-based circuitry
Auto-sensing wide voltage range
Advanced LED diagnostics
Adjustable trip delay (102A2)
Constant monitoring of single-phase, low-voltage, high-voltage (102A-9), voltage unbalance, phase reversal, harmful power line conditions
Automatically senses system voltage between 190–480 V ac. Saves setup time
Quick visual indicator for cause of trip
Prevents nuisance tripping due to rapidly fluctuating power line conditions