PLMU11

Product Status| Activei

PLMU11

3 PHASE LINE MONITOR | Series: PLMU
info
The PLMU11 continuously measures the voltage of each of the three phases to provide protection for 3-phase motors and sensitive loads. Its microcontroller senses under and overvoltage, voltage unbalance, phase loss, and phase reversal. Protection is provided even when regenerated voltages are present. Universal voltage operation from 200 to 480 VAC and standard base connection allows the PLMU11 to replace hundreds of competitive part numbers.


Operation
Upon application of power, a 0.6s random start delay begins and the PLMU11 measures the voltage levels and line frequency and selects the voltage range. The output relay is energized and the LED glows green when all voltages are acceptable and the phase sequence is correct. LED flashes green during trip delay, glows red when output de-energizes. undervoltage, overvoltage, and voltage unbalance must be sensed for continuous trip delay before the relay de-energizes. Reenergization is automatic upon fault correction. The output relay will not energize if a fault condition is sensed as 3-phase input voltage is applied. The LED alternately flashes red/green when phase reversal is sensed. Line voltage is selected with the knob, setting the over and under voltage trip points. Voltage range is automatically selected by the microcontroller.

PropertyValue
Input Voltage (V)
200 - 480 Vac
Output Form
Isolated SPDT
Termination Type
Octal 8-pin plug-in
Dimensions
3.03 H x 2.39 W x 1.78 D in. (77 x 60.7 x 45.2 mm)
Weight (kg)
0 Kg (kilogram)
Input AC Line Frequency (Hz)
50 / 60 ±2; 200 - 240 V ac: 50 / 60; 340 - 420 V ac: 50; 400 - 480 V ac: 60
Input Phase Sequence
A; B; C
Input Tolerance (%)
±15%
Input Type
3-phase delta or WYE with no connection to neutral
Input Voltage Maximum (V)
552
Output Load Rating (VA)
10 A resistive @ 240 Vac; 1/4 hp @ 125 Vac; 1/3 hp @ 250 Vac; 277 Vac max
Output Type
Energized when voltages are acceptable
Overvoltage Reset Voltage (%)
-2% of the trip voltage
Overvoltage Trip Voltage (%)
109 - 113% of the adjusted line voltage
Phase Loss
≥15%
Random Start Delay
≅0.6
Reset Time (ms)
Automatic
Response Time (ms)
Phase loss: ≤200 ms; Phase reversal: ≤200 ms
Surge Protection
IEEE C62.41-1991 Level B
Trip Delay Range
0.25 - 30 s adjustable
Trip Delay Tolerance (%)
±15%
Type of Detection
Voltage detection with delayed trip and automatic reset
Undervoltage Reset Voltage (%)
+2% of the trip voltage
Undervoltage Trip Voltage (%)
88 - 92% of the adjusted line voltage
Voltage Unbalance Reset (%)
Selected unbalance %/Reset %: 2/1.5; 3/2.5; 4/3.5; 5/4.5; 6/5.4; 7/6.3; 8/7.2; 9/8.1; 10/9
Severe Unbalance
0.25 - 2 s; disabled when the trip delay is less than 2 s
Voltage Unbalance Trip Point (%)
Adjustable 2 - 10%
Isolation Voltage
≥2500 Vrms input to output
Mounting Method
Plug-in socket rated 600V
Operating Temperature Max (°C)
60
Operating Temperature Maximum Fahrenheit
140
Operating Temperature Min (°C)
-40
Operating Temperature Minimum Fahrenheit
-40
Storage Temperature Maximum Celsius
85
Storage Temperature Maximum Fahrenheit
185
Storage Temperature Minimum Celsius
-40
Storage Temperature Minimum Fahrenheit
-40