Operation
Upon application of power, a 0.6s random start delay begins and the PLMU11 measures the voltage levels and line frequency and selects the voltage range. The output relay is energized and the LED glows green when all voltages are acceptable and the phase sequence is correct. LED flashes green during trip delay, glows red when output de-energizes. undervoltage, overvoltage, and voltage unbalance must be sensed for continuous trip delay before the relay de-energizes. Reenergization is automatic upon fault correction. The output relay will not energize if a fault condition is sensed as 3-phase input voltage is applied. The LED alternately flashes red/green when phase reversal is sensed. Line voltage is selected with the knob, setting the over and under voltage trip points. Voltage range is automatically selected by the microcontroller.
| Property | Value |
|---|---|
Input Voltage (V) | 200 - 480 Vac |
Output Form | Isolated SPDT |
Termination Type | Octal 8-pin plug-in |
Dimensions | 3.03 H x 2.39 W x 1.78 D in. (77 x 60.7 x 45.2 mm) |
Weight (kg) | 0 Kg (kilogram) |
Input AC Line Frequency (Hz) | 50 / 60 ±2; 200 - 240 V ac: 50 / 60; 340 - 420 V ac: 50; 400 - 480 V ac: 60 |
Input Phase Sequence | A; B; C |
Input Tolerance (%) | ±15% |
Input Type | 3-phase delta or WYE with no connection to neutral |
Input Voltage Maximum (V) | 552 |
Output Load Rating (VA) | 10 A resistive @ 240 Vac; 1/4 hp @ 125 Vac; 1/3 hp @ 250 Vac; 277 Vac max |
Output Type | Energized when voltages are acceptable |
Overvoltage Reset Voltage (%) | -2% of the trip voltage |
Overvoltage Trip Voltage (%) | 109 - 113% of the adjusted line voltage |
Phase Loss | ≥15% |
Random Start Delay | ≅0.6 |
Reset Time (ms) | Automatic |
Response Time (ms) | Phase loss: ≤200 ms; Phase reversal: ≤200 ms |
Surge Protection | IEEE C62.41-1991 Level B |
Trip Delay Range | 0.25 - 30 s adjustable |
Trip Delay Tolerance (%) | ±15% |
Type of Detection | Voltage detection with delayed trip and automatic reset |
Undervoltage Reset Voltage (%) | +2% of the trip voltage |
Undervoltage Trip Voltage (%) | 88 - 92% of the adjusted line voltage |
Voltage Unbalance Reset (%) | Selected unbalance %/Reset %: 2/1.5; 3/2.5; 4/3.5; 5/4.5; 6/5.4; 7/6.3; 8/7.2; 9/8.1; 10/9 |
Severe Unbalance | 0.25 - 2 s; disabled when the trip delay is less than 2 s |
Voltage Unbalance Trip Point (%) | Adjustable 2 - 10% |
Isolation Voltage | ≥2500 Vrms input to output |
Mounting Method | Plug-in socket rated 600V |
Operating Temperature Max (°C) | 60 |
Operating Temperature Maximum Fahrenheit | 140 |
Operating Temperature Min (°C) | -40 |
Operating Temperature Minimum Fahrenheit | -40 |
Storage Temperature Maximum Celsius | 85 |
Storage Temperature Maximum Fahrenheit | 185 |
Storage Temperature Minimum Celsius | -40 |
Storage Temperature Minimum Fahrenheit | -40 |
| Part Number | Part Description | RoHS | Pb-Free | RoHS (2015/863/EU) Certificate | REACH (SVHCs) Declaration | REACH (SVHCs) | Halogen Free | IPC-Material Declaration | |
|---|---|---|---|---|---|---|---|---|---|
| PLMU11 | 3 PHASE LINE MONITOR | View More |