TVM460A41S5M

Product Status| Obsoletei

TVM460A41S5M

3 PHASE LINE MONITOR | Series: TVM
info
The TVM series provides protection for motors and other sensitive loads. ontinuously measures the voltage of each of the three phases using a microcomputer circuit design that senses under and overvoltage, voltage unbalance, phase loss, and phase reversal. Protection is provided even when regenerated voltages are present. Includes a trip delay to prevent nuisance tripping and a restart delay to prevent short cycling after a momentary power outage.


Operation
Upon application of line voltage, the restart delay begins. The output relay is de-energized during restart delay. Under normal conditions, the output energizes after restart delay. Undervoltage, overvoltage, and voltage unbalance must be sensed for continuous trip delay period before the output is de-energized. The output will not de-energize if a fault is corrected during the trip delay. The restart delay begins as soon as the output relay de-energizes. If the restart delay is completed when the fault is corrected, the output relay will energize immediately. The output relay will not energize if a fault or phase reversal is sensed as 3-phase input voltage is applied.
Reset: Reset is automatic upon correction of a fault.

PropertyValue
Input Voltage (V)
460 Vac
Termination Type
0.25 in. (6.3 mm) male quick connect terminals
Dimensions
2 H x 2 W x 1.25 D in. (50.8 x 50.8 x 31.8 mm)
Weight (kg)
0 Kg (kilogram)
Dielectric Breakdown
≥2500 input to output terminals
Humidity
95% non-condensing
Input AC Line Frequency (Hz)
50 - 100
Input Phase Sequence
A; B; C
Input Type
3-phase delta or WYE with no connection to neutral
Output Load Rating (VA)
10 A resistive @ 240 Vac; 1/4 hp @ 125 Vac; 1/3 hp @ 250 Vac; 277 Vac max
Output Type
Isolated SPDT relay contacts
Overvoltage Reset Voltage (%)
≅-3% of the trip voltage
Overvoltage Trip Voltage (%)
109 - 113% of the adjusted line voltage
Phase Loss
≥25%
Power Consumption
≅3 W
Reset Time (ms)
Automatic
Response Time (ms)
Phase loss: ≤200 ms; Phase reversal: ≤200 ms
Restart Delay Range
5 m fixed
Restart Delay Tolerance (%)
±15% or ±0.2 s whichever is greater
Surge Protection
IEEE C62.41-1991 Level B
Trip Delay Range
1 s fixed
Trip Delay Tolerance (%)
±15% or ±0.1 s whichever is greater
Trip Delay vs Temperature
Trip variation: ≤±2%
Type of Detection
Voltage detection with delayed trip and automatic reset
Undervoltage Reset Voltage (%)
≅+3% of the trip voltage
Undervoltage Trip Voltage (%)
88 - 92% of the adjusted line voltage
Voltage Unbalance Reset (%)
≅-0.7% unbalance
Voltage Unbalance Trip Point (%)
4% fixed
Mounting Method
Surface mount with one #8 (M5 x 0.8) screw
Operating Temperature Max (°C)
55
Operating Temperature Maximum Fahrenheit
131
Operating Temperature Minimum Celsius
-40
Operating Temperature Minimum Fahrenheit
-40
Storage Temperature Maximum Celsius
85
Storage Temperature Maximum Fahrenheit
185
Storage Temperature Minimum Celsius
-40
Storage Temperature Minimum Fahrenheit
-40