The KSDR Series offers independent time adjustment of both delay periods. The KSDR is recommended for air drying, automatic oiling, life testing, chemical metering, and automatic duty cycling. This series is designed for general purpose commercial and industrial applications where a small, cost effective, reliable, solid-state timer is required. The factory calibration for fixed time delays is within ± 5% of the target delay. The repeat accuracy, under stable conditions, is 0.5% of the selected time delay. This series is designed for input voltages of 24, 120 or 230VAC. Time delays of 0.1 seconds to 1000 minutes are available in 6 ranges. The output is rated 1A steady and 10A inrush. The modules are totally solid state and encapsulated to protect the electronic circuitry.

Operation (Recycling - ON Time First)
Upon application of input voltage, the output energizes and the T1, ON time begins. At the end of the ON time, the output de-energizes and the T2, OFF time begins. At the end of the OFF time, the output energizes and the cycle repeats as long as input voltage is applied.
Reset: Removing input voltage resets the output and time delays, and returns the sequence to T1 ON time.

Operation (Recycling - OFF Time First)
Upon application of input voltage, the T2 OFF time begins. At the end of the OFF time, the T1 ON time begins and the load energizes. At the end of T1, T2 begins and the load de-energizes. This cycle repeats until input voltage is removed.
Reset: Removing input voltage resets the output and the sequence to T2 OFF time.

Property (Mouseover for details) Value
Input Voltage (V) 120VAC
Input Tolerance (%) ±20%
Input AC Line Frequency (Hz) 50/60Hz
Output Type Solid state
Output Load Rating (VA) 1A steady state 10A inrush at 60°C
Output Voltage Drop (V) ≅2.5V @ 1A
Time Delay Range ON time first: 10 - 1 000s; OFF: 1 - 100m
Time Delay Tolerance (%) ≤±5%
Reset Time (ms) ≤150ms
Repeat Accuracy (%) ±0.5% or 20ms whichever is greater
Setpoint vs Ambient Temperature and Operating Voltage (%) ≤ ±10%
Open State Leakage Current (A) ≅5mA @ 230VAC
Insulation Resistance ≥100 MΩ
Dielectric Breakdown ≥2000V RMS terminals to mounting surface
Circuitry Encapsulated
Power Consumption ≤2VA
Termination Type 0.25 in. (6.35mm) male quick connect terminals
Mounting Method Surface mount with one #10 (M5 x 0.8) screw
Operating Temperature -40° to 75°C (-40°F to 167°F)
Storage Temperature (F/C) -40° to 85°C (-40°F to 185°F)
Humidity 95% relative non-condensing
Dimensions 2.00 x 2.00 x 1.21 in. (50.8 x 50.8 x 30.7mm)
Weight (lbs/g) ≅2.4oz (68g)
Sample capable No