460 | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-14 | 190 - 480 Vac | 1 Form A and 1 Form B | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 360 VA @ 240 Vac B300; General Purpose: 8 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-15 | 190 - 480 Vac | 2 Form A | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 360 VA @ 240 Vac B300; General Purpose: 8 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-400HZ | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 400 | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-575 | 475 - 600 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-575-14 | 475 - 600 Vac | 1 Form A and 1 Form B | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 360 VA @ 240 Vac B300; General Purpose: 8 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-B | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-L | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-MR | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-OEM | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460-VBM | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | -3% of the trip voltage | 208 - 528 Vac | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |
460L-OEM | 190 - 480 Vac | Form C | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 0 Kg | 10 - 95% non-condensing per IEC 68-2-3 | 50 / 60 (50 will increase all delay timers by 20%) | 6 | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 107% | 110% | IP20; NEMA 1 (finger safe) | 1 - 500 s adjustable | -40° to 80°C (-40° to 176°F) | Check | Order | |