77C - 77C Series

Series: 77C
Questions? Contact Littelfuse Support
External overview image
Roll Over to Zoom
 
The 777/ 77C is a fully programmable electronic overload relay designed to protect any motor drawing 2-800 full load amps (external CTs are required above 90 amps). The 777-HVR-SP and 77C (family of products) are for single-phase 100-240VAC applications. Common applications include conveyor systems, HVAC equipment, saws and grinders, fan motors, and almost any pumping application.

All of the overload relays provide unsurpassed protection by combining overload, underload, and voltage in one package. For standalone applications, the units incorporate a 3-digit LED display that is used for programming, providing real-time operational information and displaying diagnostic codes to aid in troubleshooting a fault condition. The units also feature a communications port that can be used with communication modules listed in the 777 accessories section to form a Modbus, DeviceNet™, Profibus, or Ethernet network. Up to 99 units can be remotely monitored and controlled from a PC, PLC, or SCADA system, and data logging through a PC with the optional Solutions software. This capability allows for a simple, cost-effective way to meet new requirements for arc-flash safety.

Property (Mouseover for details) Value
Input Voltage (V) 100 - 240 Vac
Maximum Input Power 10
Input AC Line Frequency (Hz) 50 / 60
Output Form SPDT - Form C
Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
Full Load Amp Range (A) 2 - 25 (looped conductors required); 26 - 90 (direct); 91 - 800 (external CTs required)
Timing Accuracy (%) 5% ±1 s
Rapid Cycle Timer (s) 0; 2 - 500 s
Restart Delay Range After Under/Overcurrent: 2 - 500 m/s; # of Restarts: Overcurrent: 0; 1; oc1; 2; oc2; 3; oc3; 4; oc4; A (Automatic); OCA; Undercurrent: 0; 1; 2; 3; 4; A (Automatic)
Repeat Accuracy (%) Voltage: ±0.5% of nominal voltage; Current: ±1% (direct; no external CTs)
Overvoltage Trip Voltage (%) 85V - HV setting
Undervoltage Trip Voltage LV setting - 264 V
Voltage Accuracy (%) ±1%
Overcurrent Trip Point (20 - 100 A) … MULT of 80 - 120% of CT primary
Overcurrent Trip Class 5; J5; 10; J10; 15; J15; 20; J20; 30; J30; or lin (linear)
Undercurrent Trip Point 0; 10 - 98 A … MULT or 40 - 100% of CT primary
Undercurrent Trip Delay (s) 2 - 60 s
Current Accuracy (%) ±3% (<100 A direct)
Ground Fault Accuracy (%) ±15%
Sensor Hole Size Max conductor size: 0.65 in (with insulation)
Short Circuit (kA) UL: 100; CSA: 10
Surge Protection IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground
Protection Class IP20; NEMA 1 (finger safe)
Pollution Degree 3
CT Ratio 1 - 10; or 100 - 800 ratio
Address A01 - A99
Termination Type 7 in.-lbs.
Mounting Method Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature -20° to 70°C (-4° to 158°F)
Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
Humidity 10 - 95% non-condensing per IEC 68-2-3
Dimensions 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.