ALT-100-1-SW - ALT Pump Controls Series

Alt Series
Roll Over to Zoom
The ALT-xxx-1-SW and ALT-xxx-3-SW are used to alternate between two loads and are commonly used in duplex pump-up and pump-down applications to balance the runtime of both pumps. The ALT-xxx-1-SW alternating relays are 11-pin octal base plug-ins, available in two different single-phase voltage ranges. The ALT-100-1-SW is used for 95-120VAC applications and the ALT-200-1-SW is used for 190-240VAC applications. Both models are designed for a single float input and feature two isolated Form C relays (DPDT) outputs with two LEDs to indicate the energized loads.

The ALT-xxx-3-SW alternating relays are 8-pin octal base plug-ins, available in two different single-phase voltage ranges.

The ALT-100-3-SW is used for 95-120VAC applications and the ALT-200-3-SW is used for 190-240VAC applications. Both models are designed for three float inputs (lead, lag and stop floats). The lead and lag floats actuate latching relays that release when the stop float actuates. The units feature two LEDs to indicate the energized load(s).

The ALT relays have a built-in debounce time delay that prevents the relay from changing state if the float momentarily bounces, and they have a built-in switch to manually force a specific load (pump) to operate each time the input float closes. This is helpful when performing periodic maintenance or pump repair.

Property (Mouseover for details) Value
Input Voltage (V) 95 - 120 Vac
Maximum Input Power 5
Input AC Line Frequency (Hz) 50 / 60
Output Form DPDT
Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac
Debounce Time Delay (s) 1
Termination Type Torque: 12 in-lbs.; 12 - 22 AWG solid or stranded
Mounting Method DIN rail or surface mount (plug-in to OT11-PC socket)
Operating Temperature -40° to 70°C (-40° to 158°F)
Humidity 10 - 95% non-condensing per IEC 68-2-3
Dimensions 1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.