SE-330AU-00-01 - SE-330AU Series – Neutral-Earthing-Resistor Monitor Series

External overview image
Roll Over to Zoom
Disclaimer Notice

Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The SE-330AU is an advanced earth-fault and earthing-resistor monitoring relay for low- and medium-voltage transformers and generators. It monitors neutral current, neutral-to-earth voltage, and neutral-to-earth resistance. It provides continuous monitoring of the neutral-to-earth path to verify that the neutral-earthing resistor (NER) is intact. This is of utmost importance—an open NER renders current-sensing earth-fault protection inoperative and could result in a false belief that the system is functioning properly. The SE-330AU earth-fault function complies with AS/NZS 2081.3:2002. For non-AS/NZS 2081 applications, see the SE-330 or SE-330HV.

The SE-330AU New Revision provides these additional features:

  • 100 trip records with date and time stamp
  • A mini-USB interface to view measured values, configure settings and check event records using SE-MON330 v3.2 or later
  • An on-board microSD card (included) can be used for long term data logging and firmware upgrades
  • Earth-fault trip level is adjustable from 0.125 to 5A (EFCT) or 0.75 to 30A (CS30). When set to MEM, the earth-fault trip level is adjustable from 2 to 100% in 1% increments of the CT-primary rating. SE-MON330 V3.2 or later is required.
  • Dual Ethernet ports are optionally available with support for fiber and RJ45 interfaces
  • IEC 61850 protocol is optionally available
COMPUTER TO RELAY CONNECTION

Connect the SE-330AU to the network using a standard Ethernet patch cable. Use of a crossover cable to connect the SE-330AU directly to the computer running IP-Config is not recommended. A typical router will assign an IP address to all connected computers that are using DHCP. The SE-330AU does not support the use of DHCP. If the SE-330AU is being set-up for first time, it is recommended to only have one SE-330AU connected to the network to prevent communication errors.

Click here to download the COMPUTER TO RELAY CONNECTION diagram.

 

Property (Mouseover for details) Value
Analog Output Current mA 4 - 20
Communications USB
Relay Contacts Config 1 Form A; 1 Form B; 2 Form C
Supply Voltage ac 65 - 265
Supply Voltage dc 85 - 275
New Rev Avail Now
Old Rev Avail No longer available
IEEE Device Numbers 50G - 50N - 51G - 51N - 59N - 86
Relay Contacts Operation Fail-safe
Dimensions 8.4 H x 3.9 W x 5.8 D in.
Weight (lbs/g) 0 Kg
Auto Manual Reset Latching; Autoreset
Conformally coated Standard
Frequency 50; 60; ASD
GF Trip Level A 0.125 - 30.0
GF Trip Time s 0.1 - 0.5
Harmonic Filtering Standard (DFT)
Reset Type Front-panel switch/Remote N.O. Contact
RF Trip Level V 20 - 2000 (systems up to 5 kV); 100 - 10000 (systems over 5 kV)
RF Trip Time s 12
System type Resistance Grounded AC
To request product environmental information, please complete the Product Environmental Information Request Form.