102A Series - 3-Phase Voltage/Phase Monitor

External overview image
Roll Over to Zoom
Disclaimer Notice

Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The 102A is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-600VAC, 50/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range.

A unique microcontroller-based voltage and phase-sensing circuit constantly monitors the 3-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels. The Model 102A includes advanced single LED diagnostics. Five different light patterns distinguish between faults and normal conditions.

Access specifications, certifications, check availability and order parts below

Catalog #Input
Voltage (V)
Output
Form
Termination TypeMounting MethodDimensionsWeight (lbs/g)HumidityInput AC Line Frequency (Hz)Maximum Input PowerOutput Load Rating (VA)Overvoltage Reset Voltage (%)Overvoltage Trip Voltage (%)Restart Delay RangeStorage Temperature (F/C)Trip Delay RangeStockCompare
102600475 - 600 VacSPDT - 1 Form CTorque: 7 in-lbs; Wire Size: 12 - 18AWG solid or strandedSurface mountable #8 screws2.93 H x 5.27 W x 2.95 D in. (74.4 x 133.9 x 74.9 mm)0 Kg10 - 95% non-condensing per IEC 68-2-350 / 60 (50 will increase all delay timers by 20%)5Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 VacAfter a Fault: 2 s; After a Complete Power Loss: 2 s-40° to 80°C (-40° to 176°F)Under/Over Voltage: 4 s; Unbalance/Phase faults: 2 sCheck
102A190 - 480 VacSPDT - 1 Form CTorque: 7 in-lbs; Wire Size: 12 - 18 AWG#8 screws2.93 H x 5.27 W x 2.95 D in. (74.4 x 133.9 x 74.9 mm)0 Kg50 / 60 (50 will increase all delay timers by 20%)5Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 VacAfter a Fault: 2 s; After a Complete Power Loss: 2 s-40° to 80°C (-40° to 176°F)Under/Over Voltage: 4 s; Unbalance/Phase faults: 2 sCheck
102A-9190 - 480 VacSPDT - 1 Form CTorque: 7 in-lbs; Wire Size: 12 - 18 AWG#8 screws2.93 H x 5.27 W x 2.95 D in. (74.4 x 133.9 x 74.9 mm)0 Kg50 / 60 (50 will increase all delay timers by 20%)5Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac107%110%After a Fault: 2 s; After a Complete Power Loss: 2 s-40° to 80°C (-40° to 176°F)Low/High Voltage: 4 s; Unbalance/Phase faults: 2 sCheck
102A2190 - 480 VacSPDT - 1 Form CTorque: 7 in-lbs; Wire Size: 12 - 18 AWG#8 screws2.93 H x 5.27 W x 2.95 D in. (74.4 x 133.9 x 74.9 mm)0 Kg50 / 60 (50 will increase all delay timers by 20%)5Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 VacManual; 2 - 300 s adjustable-40° to 80°C (-40° to 176°F)Low/High Voltage: 4 s; Unbalance/Phase faults: 2 sCheck
102A3190 - 480 VacSPDT - 1 Form CTorque: 7 in-lbs; Wire Size: 12 - 18 AWG#8 screws2.93 H x 5.27 W x 2.95 D in. (74.4 x 133.9 x 74.9 mm)0 Kg50 / 60 (50 will increase all delay timers by 20%)5Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 VacAfter a Fault: 2 s; After a Complete Power Loss: 2 s-40° to 80°C (-40° to 176°F)Low/High Voltage: 2-30 s adjustable; Unbalance/Phase faults: 2 sCheck
To request product environmental information, please complete the Product Environmental Information Request Form.