201 SP DPDT Series - Single-Phase Voltage/Phase Monitor

External overview image
Roll Over to Zoom
The 201-xxx-SP-DPDT is an 8-pin octal-base, plug-in voltage monitor designed to protect single-phase motors regardless of size. The 201-100-SP-DPDT is used on 95-120VAC, 50/60Hz motors to prevent damage caused by low voltage. The 201-200-SP-DPDT is used on 190-240VAC, 50/60Hz motors. The units feature two isolated sets of contacts that are ideal for use with two control circuits with different voltages.

The unique microcontroller-based voltage and voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the relay’s output relays are deactivated after a specified trip delay. The output relays reactivate after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.

Access specifications, certifications, check availability and order parts below

Catalog #Input
Voltage (V)
Output
Form
Termination TypeMounting MethodDimensionsWeight (lbs/g)HumidityInput AC Line Frequency (Hz)Maximum Input PowerOutput Load Rating (VA)Restart Delay RangeStorage Temperature (F/C)Trip Delay RangeTrip Point Accuracy (%)Undervoltage Reset Voltage (%)StockCompare
201-100-SP-DPDT95 - 120 VacDPDTTorque: 12 in-lbs.; 12 - 22 AWG solid or strandedDIN rail or surface mount (plug into OT08-PC socket)1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm)0 Kg10 - 95% non-condensing per IEC 68-2-350 / 60 (50 will increase all delay timers by 20%)5Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 VacAfter a Fault or Complete Power Loss: 2 s-40° to 80°C (-40° to 176°F)Low Voltage: 4 s±1%93%Check
201-200-SP-DPDT190 - 240 VacDPDTTorque: 12 in-lbs.; 12 - 22 AWG solid or strandedDIN rail or surface mount (plug into OT08-PC socket)1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm)0 Kg10 - 95% non-condensing per IEC 68-2-350 / 60 (50 will increase all delay timers by 20%)5Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 VacAfter a Fault or Complete Power Loss: 2 s-40° to 80°C (-40° to 176°F)Low Voltage: 4 s±1%93%Check