KVM6 - KVM Series – Voltage Monitor Series

External overview image
Roll Over to Zoom
Disclaimer Notice

Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.

The KVM Series is a single-phase undervoltage monitor designed to protect sensitive equipment against brownout undervoltage conditions. The compact design and encapsulated construction make the KVM an excellent choice for OEM equipment.


Operation
The output relay is energized and the LED glows green when the input voltage is above the reset voltage threshold. If the input voltage drops below the undervoltage setpoint, the output relay and LED will de-energize. The output relay will remain de-energized as long as the input voltage is below the reset voltage. Reset is automatic when the input voltage returns to a normal range.

Property (Mouseover for details) Value
Input Voltage (V) 110 - 120 Vac; 220 - 240 Vac
Input Type Single phase
Input AC Line Frequency (Hz) 50 / 60
Output Form SPDT
Output Load Rating (VA) 8 A resistive @ 120 Vac; 1/3 hp @ 120/240 Vac
Reset Time (ms) Power off reset time ≤150 ms
Repeat Accuracy (%) ±0.5% under fixed conditions; ±1% over temperature range
Undervoltage Reset Point (%) Fixed at 209 Vac
Undervoltage Sensing Range (V) Undervoltage setpoint: 156 - 199 Vac
Voltage Sensing Accuracy (%) ±2% at 25C
Power Consumption 2.5 W @ 132 Vac; 4.5 W @ 264 Vac
Insulation Resistance ≥100
Surge Protection IEEE C62.41-1991 Level A
Termination Type 0.25 in. (6.3 mm) male quick connect terminals
Mounting Method Surface mount with one #10 (M5 x 0.8) screw
Operating Temperature -25° to 55°C (-13° to 131°F)
Storage Temperature (F/C) -40° to 85°C (-40° to 185°F)
Humidity 95% non-condensing
Dimensions 2 H x 2 W x 1.21 D in. (50.8 x 50.8 x 30.7 mm)
Weight (lbs/g) 0 Kg
Check Stock Yes
To request product environmental information, please complete the Product Environmental Information Request Form.